Start with a connected power supply and updating telemetry. Export the configuration before changing settings.
Check the connected load's voltage limits before applying a setpoint.
The interface’s allowed range does not guarantee safe operation of the load.
Allowed range
Standard VIPER limits setpoints to +/-10% of nominal. Use the range displayed for the selected device.
| Rail | Example nominal voltage | Allowed range for that nominal |
|---|---|---|
| VS1 | 12.00 V | 10.80 to 13.20 V |
| VS2 | 3.35 V | 3.02 to 3.69 V |
| VS3 | 5.00 V | 4.50 to 5.50 V |
| 3.3 V Aux | 3.30 V | 2.97 to 3.63 V |
| +12 V Aux | 12.00 V | 10.80 to 13.20 V |
| -12 V Aux | -12.00 V | -13.20 to -10.80 V |
The SRC build uses a different VS1 lower limit.
Change the value
- Open Configure and select the target slot.
- Select Read from Device.
- Record the rail’s current setpoint.
- Enter the new voltage in that rail’s setpoint field.
- Review all displayed rail values and current limits.
- Select Apply on the rail’s card.
- Check for write errors.
Some devices apply all rail setpoints together. Review every field before applying a change.
Verify and restore
- Open Telemetry and check the selected rail’s voltage.
- Confirm the output with a meter.
- After testing, enter the original setpoint and select Apply.
- Verify the restored voltage.
Written setpoints persist through input-power cycles.
Problems
| Symptom | Action |
|---|---|
| Field turns red | Enter a value within the displayed range. |
| Apply is unavailable | Select Read from Device, then enter a changed value. |
| Voltage does not change | Check output enable, inhibit, fault status, and write errors. |
| Write fails | Check communication and the hardware write-protection switch. |
| Meter and telemetry disagree | Check the measurement connections before changing calibration. |
See Hardware setup for write-protection switch positions. Contact NAI Support if the applied setting or measured output remains incorrect.